TPA GMT Fuse Panel, 4/4 TPA, 20/20 GMT, Stud Input, TPA Barrier Strip Out, GMT Set Screw Out, Power and Fuse Fail Alarm, -/+12-24V DC

TPA GMT Fuse Panel, 4/4 TPA, 20/20 GMT, Stud Input, TPA Barrier Strip Out, GMT Set Screw Out, Power and Fuse Fail Alarm, -/+12-24V DC
Click on the image above to zoom.
Part #: 8273221002
Bus Rating:
300 Amps
Number of Positions:
4 TPA + 20 GMT's/Side
Max Fuse/Breaker:
50 Amp TPA and 15 Amp GMT
Mechanical
Dimensions 19 In. [482.6mm] W x 3.5 In. [88.9mm] H x 12.125 In. [307.98mm] D
Rack Spaces 2U
Mounting Universal, 19 or 23 Inch, WECO or EIA
Offset MTG Positions Flush, 3 In. or 4 In. Offset
Finish Black Textured Powder Coat
Packaging
Packaged Width 16 In. [40.64cm]
Packaged Length 23 In. [58.42cm]
Packaged Depth 5.5 In. [13.97cm]
Electrical
Nominal Voltage -/+12-24V DC
Voltage Range -/+10-30V DC
Number of Buses 2
Bus Rating 300 Amps
Max. Interrupt Device 375 Amps
Number of Positions 4 TPA + 20 GMT's/Side
Max Fuse/Breaker 50 Amp TPA and 15 Amp GMT
Max Continuous Load 40 Amps TPA and 10.5 Amps GMT
Power Dissipation (Fully Loaded) 82.8 Watts max
Fuse/Breaker Type TPA and GMT
Extras
Load Sharing NO
Filtered NO
Volt/Current Meter NO
Connections
Input Type 2 Hole Compression Lugs, 3/8 In. Stud x 1 In. Spacing
Input Wire Range Up to 500 kcmil
Max. Terminal Width 1.40 In. max
Output Type TPA: Barrier Strip Output, GMT: Set Screw Output
Output Wire Range TPA: 6 to 22 AWG, GMT: 12 to 22 AWG
Max. Terminal Width (Output) TPA: 0.500 In. max, GMT: No Terminals Required
Chassis Ground Type 2 Hole Compression Lugs, 1/4 In. Stud x 1 In. Spacing
Ground Wire Range 2 AWG lug supplied with panel
Environmental
Short Term. Op. Temp -40° C to +70° C
Max. Ambient Up to 65° C
Storage Temperature -40° C to +70° C
Humidity Range 0 to 95% non-condensIng
Alarming
Alarm Indicators Green (Power)/Red (Alarm)
Alarm Functions Form C Relay Contacts for Remote Fuse and Power Fail Indication
Connection Type Solderless Wire Wrap (18 to 30 AWG)
Alarm Rating DC 30W/AC 50VA
Standards
Safety Type Listed
Safety Approvals UL 60950-1/UL 1801/CSA C22.2 No.60950-1/EN 60950-1/IEC 60950-1
Telcordia Approvals NEBS Level 3 (GR-63/GR-1089) and GR-3108 Class 3 (w/o salt fog testIng)
CLEI Code --
Downloads
Datasheet 8273221002.pdf
Installation Manual INS-827XXXXXXX.pdf
Datasheet: 8273221002.pdf
Installation Manual: INS-827XXXXXXX.pdf

Description

Stud In, TPA Barrier Out, GMT Set Screw Out, Power and Fuse Fail Alarm, -/+12-24V DC, Learn More…

Specification

Mechanical
Dimensions 19 In. [482.6mm] W x 3.5 In. [88.9mm] H x 12.125 In. [307.98mm] D
Rack Spaces 2U
Mounting Universal, 19 or 23 Inch, WECO or EIA
Offset MTG Positions Flush, 3 In. or 4 In. Offset
Finish Black Textured Powder Coat
Packaging
Packaged Width 16 In. [40.64cm]
Packaged Length 23 In. [58.42cm]
Packaged Depth 5.5 In. [13.97cm]
Electrical
Nominal Voltage -/+12-24V DC
Voltage Range -/+10-30V DC
Number of Buses 2
Bus Rating 300 Amps
Max. Interrupt Device 375 Amps
Number of Positions 4 TPA + 20 GMT's/Side
Max Fuse/Breaker 50 Amp TPA and 15 Amp GMT
Max Continuous Load 40 Amps TPA and 10.5 Amps GMT
Power Dissipation (Fully Loaded) 82.8 Watts max
Fuse/Breaker Type TPA and GMT
Extras
Load Sharing NO
Filtered NO
Volt/Current Meter NO
Connections
Input Type 2 Hole Compression Lugs, 3/8 In. Stud x 1 In. Spacing
Input Wire Range Up to 500 kcmil
Max. Terminal Width 1.40 In. max
Output Type TPA: Barrier Strip Output, GMT: Set Screw Output
Output Wire Range TPA: 6 to 22 AWG, GMT: 12 to 22 AWG
Max. Terminal Width (Output) TPA: 0.500 In. max, GMT: No Terminals Required
Chassis Ground Type 2 Hole Compression Lugs, 1/4 In. Stud x 1 In. Spacing
Ground Wire Range 2 AWG lug supplied with panel
Environmental
Short Term. Op. Temp -40° C to +70° C
Max. Ambient Up to 65° C
Storage Temperature -40° C to +70° C
Humidity Range 0 to 95% non-condensIng
Alarming
Alarm Indicators Green (Power)/Red (Alarm)
Alarm Functions Form C Relay Contacts for Remote Fuse and Power Fail Indication
Connection Type Solderless Wire Wrap (18 to 30 AWG)
Alarm Rating DC 30W/AC 50VA
Standards
Safety Type Listed
Safety Approvals UL 60950-1/UL 1801/CSA C22.2 No.60950-1/EN 60950-1/IEC 60950-1
Telcordia Approvals NEBS Level 3 (GR-63/GR-1089) and GR-3108 Class 3 (w/o salt fog testIng)
CLEI Code --
Downloads
Datasheet 8273221002.pdf
Installation Manual INS-827XXXXXXX.pdf